10000W 3u上架机箱系列电源参数说明
规格说明
|
输入电压
DC
|
输出电压
DC
|
最大输出电流A
|
连续
电流A
|
最大输出功率
W
|
连续输出功率
W
|
转换
效率%
|
S10KW-400/100
|
400V±15%
|
100V±1-2%
|
100
|
80
|
10000
|
8000
|
90±4%
|
S10KW-400/150
|
400V±15%
|
150V±1-2%
|
66.7
|
53.3
|
10000
|
8000
|
90±4%
|
S10KW-400/200
|
400V±15%
|
200V±1-2%
|
50
|
40
|
10000
|
8000
|
90±4%
|
S10KW-400/220
|
400V±15%
|
220V±1-2%
|
45
|
36
|
10000
|
8000
|
90±4%
|
S10KW-400/250
|
400V±15%
|
250V±1-2%
|
40
|
32
|
10000
|
8000
|
90±4%
|
S10KW-400/280
|
400V±15%
|
280V±1-2%
|
35.7
|
28.6
|
10000
|
8000
|
90±4%
|
S10KW-400/300
|
400V±15%
|
300V±1-2%
|
33
|
26
|
10000
|
8000
|
90±4%
|
S10KW-400/400
|
400V±15%
|
400V±1-2%
|
25
|
20
|
10000
|
8000
|
90±4%
|
S10KW-400/500
|
400V±15%
|
500V±1-2%
|
20
|
16
|
10000
|
8000
|
90±4%
|
S10KW-400/600
|
400V±15%
|
600V±1-2%
|
16
|
13
|
10000
|
8000
|
90±4%
|
S10KW-400/700
|
400V±15%
|
700V±1-2%
|
14
|
11
|
10000
|
8000
|
90±4%
|
S10KW-400/800
|
400V±15%
|
800V±1-2%
|
12
|
10
|
10000
|
8000
|
90±4%
|
带载率
|
建议一般工作电流比较稳定的负载,连续工作带载率控制在80%左右。动力电机类的感性,容性,功放,电台等负载带载为50%左右比较好,这类负载动态功率很大
|
工作时间
|
允许24小时不间断工作
|
过载过流
|
带载105-135%启动
|
欠压保护
|
额定输入电压-18%V以下启动
|
过压保护
|
额定输入电压+18%以上启动
|
温度保护
|
机内50度启动风扇排风,机内85度禁止输出
|
空载功耗
|
3-5W
|
空载电流
|
48V以内<0.1-0.2A,48V以上0.03A-0.1范围
|
过载保护
|
过载105%~135%进入保护范围
|
启动时间
|
3-5S (软启动)
|
抗震性
|
10~500Hz,2G 10秒/1周期,共60分钟,各轴
|
耐压
|
输入输出间:1.5KVAC,输入与外壳:1.5KVAC输出与外壳:0.5KVAC
|
隔离情况
|
输入与输出隔离状态;
|
隔离电阻
|
输入输出间,输入与外壳,输出与外壳:500VDC/100M Ohms
|
工作温/湿度
|
-30℃~+65℃,20%~90%RH
|
储存温/湿度
|
-40℃~+85℃,10%~95%%RH
|
外形尺寸
|
机身440*350*130mm
|
外壳材料
|
铝合金
|
整机净重
|
9.0 Kg
|
安全标准
|
测试标准:EN55015 EN61547 EN61000-3-2 EN6100-3-3
证书编号:SHBST2011101811YEC-1
|
EMC标准
|
测试标准:EN61347-1 EN61347-2-13
证书编号:SHBST2011101811YEC-2
|
|